Silent features

The company has set up a state of art manufacturing facility at IMT Manesar (Gurgaon) for manufacturing of electrical control panels.

These are manufactured on floor area of 32000 Square feet, spread in 2 floors.

The products are manufactured using latest CNC Turrent punch press and bending press specially imported from 'AMADA' Japan. The sheet metal is pre treated with eight tank process and then powder coated on conveyrsid power coating plant.

The switchgear is then mounted on the sheet metal, so provided and complete with necessary wiring as per control circuit is provided.

Our products are duly approved by CPRI Bhopal and confirms to Indian standard IS 8623.


Range of Products Manufactured By Us

  • All types of Electrical switch boards, power control center, capacitor and power resistor, Feeder pillars with PLC automation systems.
  • Busduct and rising mains.
  • Automains failure, DG Synchronizing, Pump automation, motor starter panels.
  • Load and power distribution centers with PLC based synchronization of multiple DG Sets.

Technical Specification

Application Standard IS-8623 part-I
IS-4237
IS-375
IS-13947
System Votage Up to 500V 3 Ph 50/60Hz, ¾ Wire System
Insulation Voltage 660 V
Ambient Temperature Upto 55 Deg. C (standard 40 Deg. C)
Continuous Current rating Upto 4000A
ACBs Panels up to 6000A
Fault Withstand 50 KA for 1 Second
Degree of Protection Up to IP-54
IP-55 (For small panels and Panels for out
door application)
Enclosure 14/16SWG as standard
12/10SWG on request
Bus bars Aluminum E91E as per IS-5082 (Standard) Copper as per IS-1897 on request.
Construction Standard Design-Compartmentalized/
cubical design and modular construction.
Horizontal Bus Bar Chamber At TOP/ Bottom or both
Vertical Bus Bar Chamber Front/Rear as per requirements
Feeder Execution Fixed/Draw out as per requirements
Cable Entry Front Cable alley/Rear Cable entry/
Top/bottom as per requirements.

Tests


Routine tests are conducted on power control centers in accordance with IS : 8623 and comprise of-

  • Inspection of the power control center including inspection of wiring and electrical operational tests, where necessary.
  • Dielectric tests with high voltage tester.
  • Insulation test with 1000 volts / 500 volt megger.
  • Checking of protective measures and electrical continuity of protective circuits.

Standards

The equipment designed to confirm the following standards :-

  • IS: 8623-Factory Built Assemblies of Switchgear and Control Gear.
  • IS: 375-Marking and Arrangement for Switchgear Bus Bar etc.
  • IS: 2147- Degree of Protection provided by enclosure for low voltage Switchgear and Control Gear.
  • IS: 2516-Air Circuit Breakers of voltages not exceeding 1000V AC.
  • IS: 4064- Fuse Switch and Switch Fuse Units for voltage not exceeding 1000V AC.
  • IS: 9224- H.R.C. fuse links.
  • IS: 2705-Current Transformers.
  • IS: 1248- Indicating Instruments.
  • IS: 6875- Control Switches & Push Buttons.
  • IS: 4237- General requirements for Switch Gear & Control Gear.